• Compact Vector control Drive Ratings:

    • 200V:
      > 1Ph: 0.1 to 2.2 kW
      > 3Ph: 0.1 to 15kW
    • 400V:
      > 3Ph: 0.2 to 15kW

    V1000 is a general purpose inverter drive covering the demands of a wide field of applications including Open-Loop-Vector functionality and the usage of PM motor without feedback

    Features

    • High flux braking for 50% reduction of braking time
    • Quick response on load and speed changes to improves machine performance.
    • Online Auto-Tuning to optimise for improved motor performance at low speed
    • Open Loop Vector Control for PM motor operation.
    • Safe Disable Inputs for Safe Torque OFF

    Normal Duty Applications

    Heavy Duty Applications

    Download

  • Compact Vector control Drive

    200V Single Phase

    V1000 Model number PND(kW) IND(A) PHD(kW) IHD(A)
    CIMR-VTBA0001BAA 0.2 1.2 0.1 0.8
    CIMR-VTBA0002BAA 0.4 1.9 0.2 1.6
    CIMR-VTBA0003BAA 0.75 3.3 0.4 3.0
    CIMR-VTBA0006BAA 1.1 6.0 0.75 5.0
    CIMR-VTBA0010BAA 2.2 9.6 1.5 8.0
    CIMR-VTBA0012BAA 3 12 2.2 11

    200V Three Phase

    V1000 Model number PND(kW) IND(A) PHD(kW) IHD(A)
    CIMR-VT2A0001BAA 0.2 1.2 0.1 0.8
    CIMR-VT2A0002BAA 0.4 1.9 0.2 1.6
    CIMR-VT2A0004BAA 0.75 3.5 0.4 3
    CIMR-VT2A0006BAA 1.1 6 0.75 5
    CIMR-VT2A0010BAA 2.2 9.6 1.5 8
    CIMR-VT2A0012BAA 3 12 2.2 11
    CIMR-VT2A0020BAA 5.5 19.6 3.7 17.5
    CIMR-VT2A0030FAA 7.5 30 5.5 25
    CIMR-VT2A0040FAA 11 40 7.5 33
    CIMR-VT2A0056FAA 15 56 11 47
    CIMR-VT2A0069FAA 18.5 69 15 60

    400V Single Phase

    V1000 Model number PND(kW) IND(A) PHD(kW) IHD(A)
    CIMR-VT4A0001BAA 0.4 1.2 0.2 1.2
    CIMR-VT4A0002BAA 0.75 2.1 0.4 1.8
    CIMR-VT4A0004BAA 1.5 4.1 0.75 3.4
    CIMR-VT4A0005BAA 2.2 5.4 1.5 4.8
    CIMR-VT4A0007BAA 3 6.9 2.2 5.5
    CIMR-VT4A0009BAA 3.7 8.8 3 7.2
    CIMR-VT4A0011BAA 5.5 11.1 3.7 9.2
    CIMR-VT4A0018FAA 7.5 17.5 5.5 14.8
    CIMR-VT4A0023FAA 11 23 7.5 18
    CIMR-VT4A0031FAA 15 31 11 24
    CIMR-VT4A0038FAA 18.5 38 15 31
  • Control Characteristics
    Product V1000
    Type Compact Vector Control Drive
    Rated Output Voltage (dependent on input) Three Ph 200V Class : 200 to 240VAC
    Three Ph 400V Class : 380 to 480VAC
    Single Ph 200V Class : 200 to 240VAC
    Motor Types Induction Motor, Permanent Magnet Motor (IPM/SPM)
    Control Methods Open Loop Vector Control (Current Vector), V/f Control, PM Open Loop Vector Control (for SPM and IPM motors)
    Speed Control Range 1:100 (Open Loop Vector Control), 1:20 to 40 (V/f Control), 1:10 (PM Open Loop Vector Control)
    Starting Torque 200% / 0.5 Hz (assumes Heavy Duty rating IM of 3.7 kW or less using Open Loop Vector Control),
    50% / 6 Hz (assumes PM Open Loop Vector Control)
    Frequency Range 0 to 400Hz
    Frequency Accuracy Digital reference: within ±0.01% of the max. output frequency (-10°C to +50°C)
    Analog reference: within ±0.1% of the max. output frequency (25°C±10°C)
    Frequency Setting Resolution Main frequency reference: 0 to 10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
    Main speed reference : Pulse Train Input (max. 32 kHz)
    Output Frequency
    Resolution
    20 bit of maximum output frequency (parameter E1-04 setting)
    Torque Limit Open Loop Vector Control allows separate settings in four quadrants
    Accel/Decel time 0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
    Environmental Factors
    Ambient Temperature −10 to +50˚C (open chassis), −10 to +40˚C (enclosure)
    Altitude Up to 1000 meters
    Humidity 95 RH% or less (no condensation)
    Shock 10 to less than 20 Hz (9.8 m/s2) max., 20 to 55 Hz (5.9 m/s2) max.
    Area of Use Indoors
    Protection Features 
    Motor Protection Motor overheat protection based on output current
    Momentary Overcurrent
    Protection
    Drive stops when output current exceeds 200% of Heavy Duty Rating
    Overload Protection Drive stops after 60 s at 150% of rated output current (Heavy Duty Rating)
    Overvoltage Protection 200 V class: Stops when DC bus exceeds approx. 410 V
    400 V class: Stops when DC bus exceeds approx. 820 V (approx. 740 V when power supply voltage is less than 400 V)
    Undervoltage Protection Three-phase 200 V class: Stops when DC bus falls below approx. 190 V
    Single-phase 200 V class: Stops when DC bus falls below approx. 160 V
    Three-phase 400 V class: Stops when DC bus falls below approx. 380 V (approx. 350 V when the power supply voltage is less than 400 V)
    Momentary Power Loss
    Ride-Thru
    Stops after approx. 15 ms (default). Parameter settings allow the drive to continue running if power loss lasts for up to approx. 2 s 
    Heatsink Overheat
    Protection
    Thermistor
    Stall Prevention Separate settings allowed during acceleration, and during run. Enable/disable only during deceleration.
    Ground Fault Protection Protection by electronic circuit
    Charge LED Charge LED remains lit until DC bus has fallen below approx. 50 V
    Standards Compliance UL508C
    IEC/EN61800-3,IEC/EN61800-5-1
    ISO/EN13849-1 Cat.3 PLd,IEC/EN61508 SIL2
    Power Specifications
    Rated input Voltage/Frequency Three-phase AC power supply 380 to 480 V 50/60 Hz ; DC power supply: 510 to 680 V
    Three-phase AC power supply 200 to 240 V 50/60 Hz ; DC power supply: 270 to 340 V
    Single-phase AC power supply 200 to 240 V 50/60 Hz ; DC power supply: 270 to 340 V 
    Allowable Voltage
    Fluctuation
    −15% to 10%
    Allowable Frequency
    Fluctuation
    ±5%
    Common Specifications
    Carrier Frequency 2 kHz (user-set, 2 to 15 kHz possible)
    Multi Funcction Digital Inputs 7 Digital Inputs ( NPN or PNP ) , 24VDC. 
    Multi Function Digital Outputs P1,P2 – PC Photocoupler Output (48 Vdc (or less), 50 mA (or less)) and
    1 fault relay MA-MB-MC (Digital output 30 Vdc (or less), 10 mA to 1 A ,250 Vac (or less), 10 mA to 1 A)
    Multi Function Analog Inputs 2 Multi function Analog input A1 (0 to 10 Vdc (20 kΩ) resolution: 1/1000) &  A2  ( 0 to 10 Vdc (20 kΩ) resolution: 1/1000, 4 to 20 mA or 0 to 20 mA (250 Ω) resolution: 1/500)
    Multi Function Analog Output 1 Multi function Analog outputs  AM-AC (0 to 10 Vdc (2 mA or less)Resolution: 1/1000))
    Pulse Train  1 Pusle Train output (0.5 to 32 kHz)
    1 Pulse Train input (max 32 kHz)
    Programming Interface Serial port or USB B port in front of VFD
    Serial communication MEMOBUS/Modbus (RTU mode) comm. RS-485, Max. 115.2 kbps
    Optional communication Protocols MECHATROLINK-II,MECHATROLINK-III,CC-Link, DeviceNet, CompoNet, PROFIBUS-DP , CANopen , EtherCAT,EtherNet/IP, Modbus/TCP
    Additional Functions Momentary power loss ride-thru, Speed search, Overtorque detection, Torque limit, 17-step speed (max),Accel/decel time switch, S-curve accel/decel, 3-wire sequence, Auto-tuning (rotational, stationary tuningfor resistance between lines), Dwell, Cooling fan on/off switch, Slip compensation, Torque compensation,Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop,Overexcitation braking, High slip braking, PID control (with sleep function), Energy saving control, MEMOBUS comm. (RS-485/422 max, 115.2 kbps), Fault restart, Application presets, DriveWorksEZ (customized function),Removable terminal block with parameter backup function.

     

  • Compact Vector control Drive Ratings:

    • 200V:
      > 1Ph: 0.1 to 2.2 kW
      > 3Ph: 0.1 to 15kW
    • 400V:
      > 3Ph: 0.2 to 15kW

    V1000 solar drive is used for solar pump applications

    • Suitable for BLDC and PM motor
    • Suitable for surface mount and submersible pump for 3 Phase 200Volts/400volts induction motor
    • wide range capacity from 0.1kW to 18.5kW
    • All day run stop restart mode management
    • Diagnostics and self protection features.
    • Protection against dry run of pump
    • Simple and faster installation and commissioning.
      V1000 Solar Technical Electrical specification
    Pump inverter type V/F control with derived MPPT Technology
    Dual supply ( Grid/ Solar) Change over Available
    input DC voltage ( VOC) 400volts DC for 200volts Class and 800volts class for 400 volts drive
    input DC voltage ( Vmp) 280 VDC tp 310 V Dc /510 V dc to 620 V DC
    Input DC cuttent and power As per motor capacity
    Min frequency 0hz selectable setting range
    Max frequency 120Hz
    Shock 10 to less than 20 Hz (9.8m/s2) max
    output Ac voltage 3 phase 190-240v (-15%.+10%)/380-480V/(-15%,+10%)
    Output Ac voltage As per chart above
    Motor frequency 0-60Hz
    Motor control technology V/f Control
    MPPT voltage 230V to 360 V for 200 volts

    460V to 620 V for 400 volts

    Over load capacity 120% for ND
    Under voltage 125V DC for 200 volts Class/ 250 for 400 volts Class
    Protection Dry run , short circuit, Open Phase in input & output side, High Voltage, Low voltage and over load , earthing, recerse polarity.
    Ambient temp -10deg to 50 deg
    Relative humidity Max 95% relative humanity